Home |
Search |
Today's Posts |
#1
![]()
posted to rec.boats.building
|
|||
|
|||
![]()
I posted this on another bulletin where a contributor had bonded all
his underwater metal with 1" copper straps and needed to test. Copied here for anyone having electrolysis problems. An ohm meter is a poor way to check bonding connections. I use a 12 volt lamp and make a probe using a screwdriver. Hook a long enough wire to the positive terminal of the starting battery and then poke the screwdriver into each of the through hull fittings and make sure the lamp lights. An ohm meter is only testing the circuit at micro- amps. The following applies mainly to boats left in the water. Trailered boats rarely spend enough time in the water for electrolysis to be a problem. ELECTROLYSIS 101. I've worked with electrolysis for 18 years including live-aboard on a steel yacht for 14. We have sold thousands of our galvanic isolators and handle numerous emails/phone calls daily on electrolysis situations. BONDING STRAPS Although your copper straps look impressive they are totally unnecessary. The wire at the most only carries a few milliamps and there is no concern for voltage drop so the copper only needs to be heavy enough to resist deterioration from oxidation. A 10 gauge copper wire is more than adequate. I use non stranded 10 gauge bare copper wire for my installations, being careful to secure it so it is not subject to flexing from boat motion. Non stranded wire has much less surface area and avoids the cavities between the strands where moisture and corrosion/oxidation can progress. THEORY Electrolysis only happens when two dissimilar metals are immersed in an electrolyte and connected together. The dissimilar metals have different electrolysis voltages so if you connect them together current flows through the connecting wire one direction and through the water the other. As the current leaves one metal to travel to the other, it causes metal to come off one surface and be deposited on the other like battery plates so the higher voltage metal suffers electrolysis. Electrolysis can also occur when an adjacent structure or boat is injecting DC current into the water and that current goes in one end of your boat and out the other on its way to the destination. This can cause electrolysis even though your boat is not an offender. PROTECTION There are basically 2 ways to reduce electrolysis. The PREFERABLE one is to DISCONNECT the electrical circuit. If this can't be done, the second method is to provide a sacrificial anode (Zinc) so it deteriorates rather than your expensive equipment. a) DISCONNECTING Electrolysis cannot occur on an isolated piece of metal in salt water. It is all at the same voltage but if it is isolated no current can flow so there is no electrolysis. When it is connected to another piece of metal, ESPECIALLY if the other piece is a different metal, you just created a shorted battery and electrolysis will start. By following the wrong advise and bonding everything in the boat you are creating batteries where it is unnecessary and making electrolysis problems worse. ANN-MARIE'S RULE #1. Only bond underwater items that are showing symptoms of electrolysis. If it ain't broke, DON'T fix it. Once you bond it unnecessarily you have CREATED the circuit rather than DISCONNECTING it. You are now stuck with providing Zincs since you have removed the first line of protection. Although some through hulls appear to be isolated due to sitting in fiberglass and using non-metallic tubing, they quite often are not and WILL need bonding. For example the raw water cooling inlet for an inboard engine is in fact connected to the engine block by the salt water in the tubing and may need bonding so the current flows though copper rather than the water and in/out of the through hull. b) SACRIFICIAL ZINC There are situations where different metals cannot be disconnected and you are stuck with putting zincs on them to provided a target for the electrolysis. Zincs have a higher electrolytic voltage than marine metals so it is the first to deteriorate. Keep in mind that the zinc will CREATE electrolysis (favorable electrolysis since the zinc is being eaten up). Putting zincs where they were not needed will still cause the zincs to erode away since they create the battery situation where none may have existed. The range of protection a zinc can supply to other metals bonded to it is limited by the conductivity of the water. In salt water you get coverage for a radius of about 4 to 6 feet. A zinc on the stern of a 14 ft boat where everything is bonded is only protecting half the boat. This range gets even less in fresh water and may reduce to only inches. Often magnesium is substituted for zinc in fresh water to provide an even higher voltage to push through the fresh water. USE A CONDOM Over 90% of our customers electrolysis problems are created by the shore power connection. You could theoretically disconnect the ground connection in the shore power and avoid electrolysis (and in some cases this is a solution) but ABYC regulations require the AC ground be connected to the DC ground so an electrical fault on the boat won't electrocute swimmers in the vicinity. When you connect your underwater metal to the shore power ground you have "bonded" with every other boat on the docks who have the same connection. Now electrolysis currents are free to flow anywhere in the marina and it only takes one boat with a 12 volt DC leakage to eat up every boat within a wide radius even though the offender has zero electrolysis evidence. Your protection is a Galvanic Isolator in the ground connection of the shore power lead. You don't have to purchase ours (although they are typically less than 1/2 the price of our competitors). Any Galvanic Isolator that meets AYBC specifications will do - they are not rocket science and extremely reliable. We have sold thousands, all on unconditional warranty and have never had a return due to failure. Feel free to ask general interest questions here or email me if you prefer. |
#2
![]()
posted to rec.boats.building
|
|||
|
|||
![]()
Andina,
I found your synopsis of this issue very good. This problem is not understood by most people. Please explain what a Galvanic Isolator is. I find absolutely no reason to connect shore earth to your boat, ever. There should be a ships earth and it should never be the hull, either on the AC side or the DC side. The ships earth should be insolated from the hull. There should be an LED mounted in an obvious location connected between the hull and ships earth. Normally this LED would be off, unless there is a DC leak to the hull. This would then allow the LED to turn on and alert the crew to locate the fault immediately. On the AC side, an isolation transformer is a necessity. The ships safety earth is then bonded to nuetral at the panel only and the main ships ckt breaker should be of the GFI type. Steve "Andina Marie" wrote in message ... I posted this on another bulletin where a contributor had bonded all his underwater metal with 1" copper straps and needed to test. Copied here for anyone having electrolysis problems. An ohm meter is a poor way to check bonding connections. I use a 12 volt lamp and make a probe using a screwdriver. Hook a long enough wire to the positive terminal of the starting battery and then poke the screwdriver into each of the through hull fittings and make sure the lamp lights. An ohm meter is only testing the circuit at micro- amps. The following applies mainly to boats left in the water. Trailered boats rarely spend enough time in the water for electrolysis to be a problem. ELECTROLYSIS 101. I've worked with electrolysis for 18 years including live-aboard on a steel yacht for 14. We have sold thousands of our galvanic isolators and handle numerous emails/phone calls daily on electrolysis situations. BONDING STRAPS Although your copper straps look impressive they are totally unnecessary. The wire at the most only carries a few milliamps and there is no concern for voltage drop so the copper only needs to be heavy enough to resist deterioration from oxidation. A 10 gauge copper wire is more than adequate. I use non stranded 10 gauge bare copper wire for my installations, being careful to secure it so it is not subject to flexing from boat motion. Non stranded wire has much less surface area and avoids the cavities between the strands where moisture and corrosion/oxidation can progress. THEORY Electrolysis only happens when two dissimilar metals are immersed in an electrolyte and connected together. The dissimilar metals have different electrolysis voltages so if you connect them together current flows through the connecting wire one direction and through the water the other. As the current leaves one metal to travel to the other, it causes metal to come off one surface and be deposited on the other like battery plates so the higher voltage metal suffers electrolysis. Electrolysis can also occur when an adjacent structure or boat is injecting DC current into the water and that current goes in one end of your boat and out the other on its way to the destination. This can cause electrolysis even though your boat is not an offender. PROTECTION There are basically 2 ways to reduce electrolysis. The PREFERABLE one is to DISCONNECT the electrical circuit. If this can't be done, the second method is to provide a sacrificial anode (Zinc) so it deteriorates rather than your expensive equipment. a) DISCONNECTING Electrolysis cannot occur on an isolated piece of metal in salt water. It is all at the same voltage but if it is isolated no current can flow so there is no electrolysis. When it is connected to another piece of metal, ESPECIALLY if the other piece is a different metal, you just created a shorted battery and electrolysis will start. By following the wrong advise and bonding everything in the boat you are creating batteries where it is unnecessary and making electrolysis problems worse. ANN-MARIE'S RULE #1. Only bond underwater items that are showing symptoms of electrolysis. If it ain't broke, DON'T fix it. Once you bond it unnecessarily you have CREATED the circuit rather than DISCONNECTING it. You are now stuck with providing Zincs since you have removed the first line of protection. Although some through hulls appear to be isolated due to sitting in fiberglass and using non-metallic tubing, they quite often are not and WILL need bonding. For example the raw water cooling inlet for an inboard engine is in fact connected to the engine block by the salt water in the tubing and may need bonding so the current flows though copper rather than the water and in/out of the through hull. b) SACRIFICIAL ZINC There are situations where different metals cannot be disconnected and you are stuck with putting zincs on them to provided a target for the electrolysis. Zincs have a higher electrolytic voltage than marine metals so it is the first to deteriorate. Keep in mind that the zinc will CREATE electrolysis (favorable electrolysis since the zinc is being eaten up). Putting zincs where they were not needed will still cause the zincs to erode away since they create the battery situation where none may have existed. The range of protection a zinc can supply to other metals bonded to it is limited by the conductivity of the water. In salt water you get coverage for a radius of about 4 to 6 feet. A zinc on the stern of a 14 ft boat where everything is bonded is only protecting half the boat. This range gets even less in fresh water and may reduce to only inches. Often magnesium is substituted for zinc in fresh water to provide an even higher voltage to push through the fresh water. USE A CONDOM Over 90% of our customers electrolysis problems are created by the shore power connection. You could theoretically disconnect the ground connection in the shore power and avoid electrolysis (and in some cases this is a solution) but ABYC regulations require the AC ground be connected to the DC ground so an electrical fault on the boat won't electrocute swimmers in the vicinity. When you connect your underwater metal to the shore power ground you have "bonded" with every other boat on the docks who have the same connection. Now electrolysis currents are free to flow anywhere in the marina and it only takes one boat with a 12 volt DC leakage to eat up every boat within a wide radius even though the offender has zero electrolysis evidence. Your protection is a Galvanic Isolator in the ground connection of the shore power lead. You don't have to purchase ours (although they are typically less than 1/2 the price of our competitors). Any Galvanic Isolator that meets AYBC specifications will do - they are not rocket science and extremely reliable. We have sold thousands, all on unconditional warranty and have never had a return due to failure. Feel free to ask general interest questions here or email me if you prefer. |
#3
![]()
posted to rec.boats.building
|
|||
|
|||
![]()
On Jan 6, 6:06 am, "Steve Lusardi" wrote:
Andina, I found your synopsis of this issue very good. This problem is not understood by most people. Please explain what a Galvanic Isolator is. I find absolutely no reason to connect shore earth to your boat, ever. There should be a ships earth and it should never be the hull, either on the AC side or the DC side. The ships earth should be isolated from the hull. There should be an LED mounted in an obvious location connected between the hull and ships earth. Normally this LED would be off, unless there is a DC leak to the hull. This would then allow the LED to turn on and alert the crew to locate the fault immediately. On the AC side, an isolation transformer is a necessity. The ships safety earth is then bonded to neutral at the panel only and the main ships ckt breaker should be of the GFI type. Steve REPLY from ANDINA. A Galvanic isolator consists of back to back diodes which still provide an electrical path for AC current but block DC voltages up to about 1 volt. So the ground protection for electrical faults is retained but the small DC voltages that cause electrolysis are blocked. ABYC specifications require that the Galvanic Isolator be able to carry 130% of rated current continuously. This is required because if an appliance on a boat was wired incorrectly and using the ground instead of the neutral, the total current would be flowing through the isolator. Should the isolator then fail under load, the AC would now be connected directly to the ground that has become disconnected from the shore ground. This puts 120 volts AC on all the underwater items on your boat which can KILL SWIMMERS IN THE VICINITY. Your statement that:- I find absolutely no reason to connect shore earth to your boat, ever. is very dangerous without explanation. Omitting this connection can kill people. On most boats you cannot isolate the DC ground from the underwater metal because the starter motor is bolted to the engine block which in turn connects to the propeller shaft and the water. So without the ground, an internal failure of the battery charger could put 120 or 230 volts AC on your DC ground and into the water. Relying on indicators or alarms is not a satisfactory solution, it only takes milliseconds to kill someone. Relying on a GFI Circuit breaker is not satisfactory. In salt water the current flowing though a GFIC can kill a swimmer before the GFIC can trip. Now I agree that the probability of these worst case scenarios is remote, however the consequences are grim. The ABYC specifications err on the conservative side to avoid leaving the risk/consequence decision up to the boat owner. If using an isolation transformer the risk is miniscule. Isolation transformers are extremely reliable, the only risk would be an uninformed installer making an error in wiring up equipment. Without the isolation transformer and with no ground you are betting the reliability of your equipment against the life of swimmers in the vicinity of your boat. Regards, Ann-Marie Foster, |
#4
![]()
posted to rec.boats.building
|
|||
|
|||
![]()
On Sun, 6 Jan 2008 08:05:44 -0800 (PST), Andina Marie
wrote: .... Relying on a GFI Circuit breaker is not satisfactory. In salt water the current flowing though a GFIC can kill a swimmer before the GFIC can trip. .... Regards, Ann-Marie Foster, Do you have a reference supporting the lethality of GFIs to swimmers, Ann-Marie? Brian Whatcott Altus OK |
#5
![]()
posted to rec.boats.building
|
|||
|
|||
![]()
I run an Isolation transformer and I use an air starter.
Steve "Andina Marie" wrote in message ... On Jan 6, 6:06 am, "Steve Lusardi" wrote: Andina, I found your synopsis of this issue very good. This problem is not understood by most people. Please explain what a Galvanic Isolator is. I find absolutely no reason to connect shore earth to your boat, ever. There should be a ships earth and it should never be the hull, either on the AC side or the DC side. The ships earth should be isolated from the hull. There should be an LED mounted in an obvious location connected between the hull and ships earth. Normally this LED would be off, unless there is a DC leak to the hull. This would then allow the LED to turn on and alert the crew to locate the fault immediately. On the AC side, an isolation transformer is a necessity. The ships safety earth is then bonded to neutral at the panel only and the main ships ckt breaker should be of the GFI type. Steve REPLY from ANDINA. A Galvanic isolator consists of back to back diodes which still provide an electrical path for AC current but block DC voltages up to about 1 volt. So the ground protection for electrical faults is retained but the small DC voltages that cause electrolysis are blocked. ABYC specifications require that the Galvanic Isolator be able to carry 130% of rated current continuously. This is required because if an appliance on a boat was wired incorrectly and using the ground instead of the neutral, the total current would be flowing through the isolator. Should the isolator then fail under load, the AC would now be connected directly to the ground that has become disconnected from the shore ground. This puts 120 volts AC on all the underwater items on your boat which can KILL SWIMMERS IN THE VICINITY. Your statement that:- I find absolutely no reason to connect shore earth to your boat, ever. is very dangerous without explanation. Omitting this connection can kill people. On most boats you cannot isolate the DC ground from the underwater metal because the starter motor is bolted to the engine block which in turn connects to the propeller shaft and the water. So without the ground, an internal failure of the battery charger could put 120 or 230 volts AC on your DC ground and into the water. Relying on indicators or alarms is not a satisfactory solution, it only takes milliseconds to kill someone. Relying on a GFI Circuit breaker is not satisfactory. In salt water the current flowing though a GFIC can kill a swimmer before the GFIC can trip. Now I agree that the probability of these worst case scenarios is remote, however the consequences are grim. The ABYC specifications err on the conservative side to avoid leaving the risk/consequence decision up to the boat owner. If using an isolation transformer the risk is miniscule. Isolation transformers are extremely reliable, the only risk would be an uninformed installer making an error in wiring up equipment. Without the isolation transformer and with no ground you are betting the reliability of your equipment against the life of swimmers in the vicinity of your boat. Regards, Ann-Marie Foster, |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
![]() |
||||
Thread | Forum | |||
researching live-aboard cruising boats | Cruising | |||
researching live-aboard cruising boats | General | |||
C-Dory and rough water boats | General | |||
water pickup for washdown&live well | General | |||
Salt water and Fibreglass Boats | General |