#1
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
I can't figure it out. I keep having to let refrigerant out of my Adler Barbour. It runs great with the suction-side pressure set at 15 psi. But, every month or so it will commence to cycle off and on after being off for the night. I put a gauge on it and the suction side pressure is in the beginning of the red range(55 psi). It turns on and the compressor starts compressing, the pressure starts going down but it only gets to about 45 psi until the compressor *clicks off* and the voltage gauge goes up a volt or two because the load comes off the circuit. Then it turns itself off and back on and the compressor starts to compress again and the pressure goes down to about 45 psi, then it cycles off again. So, I let out some pressure until it only starts out around 45 psi and it will finally keep compressing until it draws down the suction side to about 15 psi where it stabilizes. So where does the extra pressure come from. I've had to let out ten pounds of pressure about half a dozen times this summer. I can understand leaks but this is ridiculous! -- Sir Gregory |
#2
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
On Thu, 02 Oct 2014 15:14:32 -0400, "Sir Gregory Hall, Esq."
wrote: I can't figure it out. I keep having to let refrigerant out of my Adler Barbour. It runs great with the suction-side pressure set at 15 psi. But, every month or so it will commence to cycle off and on after being off for the night. I put a gauge on it and the suction side pressure is in the beginning of the red range(55 psi). It turns on and the compressor starts compressing, the pressure starts going down but it only gets to about 45 psi until the compressor *clicks off* and the voltage gauge goes up a volt or two because the load comes off the circuit. Then it turns itself off and back on and the compressor starts to compress again and the pressure goes down to about 45 psi, then it cycles off again. So, I let out some pressure until it only starts out around 45 psi and it will finally keep compressing until it draws down the suction side to about 15 psi where it stabilizes. So where does the extra pressure come from. I've had to let out ten pounds of pressure about half a dozen times this summer. I can understand leaks but this is ridiculous! You have a closed system connected to a compressor. One side to the suction side and the other to the pressure side. Think why the suction side would be at a higher pressure, or conversely, why the low pressure side is at a lower pressure in a properly operating system. -- Cheers, Bruce in Bangkok |
#3
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
|
#5
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
On Sat, 04 Oct 2014 07:34:51 +0700, wrote:
On Fri, 03 Oct 2014 10:38:12 -0400, "Sir Gregory Hall, Esq." wrote: On Fri, 03 Oct 2014 19:08:56 +0700, wrote: On Thu, 02 Oct 2014 15:14:32 -0400, "Sir Gregory Hall, Esq." wrote: I can't figure it out. I keep having to let refrigerant out of my Adler Barbour. It runs great with the suction-side pressure set at 15 psi. But, every month or so it will commence to cycle off and on after being off for the night. I put a gauge on it and the suction side pressure is in the beginning of the red range(55 psi). It turns on and the compressor starts compressing, the pressure starts going down but it only gets to about 45 psi until the compressor *clicks off* and the voltage gauge goes up a volt or two because the load comes off the circuit. Then it turns itself off and back on and the compressor starts to compress again and the pressure goes down to about 45 psi, then it cycles off again. So, I let out some pressure until it only starts out around 45 psi and it will finally keep compressing until it draws down the suction side to about 15 psi where it stabilizes. So where does the extra pressure come from. I've had to let out ten pounds of pressure about half a dozen times this summer. I can understand leaks but this is ridiculous! You have a closed system connected to a compressor. One side to the suction side and the other to the pressure side. Think why the suction side would be at a higher pressure, or conversely, why the low pressure side is at a lower pressure in a properly operating system. Since the two sides are able to equalize when the compressor sits idle overnight the suction side and the compressed side should be the same. So, when I measure the suction side at startup and it shows 50 psi that means the compressed side is also (temporarily) at 50. As the suction side pressure decreases the compressed side increases. So, if I measured pressure on the suction side in Jult after it has sat idle all night it and it starts out being 30psi, do tell why in August it will suddenly be reading 50psi on the same suction side at start up? As I said, it IS a closed system. If the system has been off for a sufficient period the entire system should be the same pressure as the refrigerant will be the same temperature throughout the system. Then you start the system and the compressor sucks on one side and blows on the other as it is a closed system why aren't the two sides of the system still at the same pressure? I fear you may suffer from reading comprehension problems, Bruce. I understand what you just typed and the problem has nothing to do with a system that's running and everything to do with a system that has been turned off for the night. In the morning, before starting, when the system is stabilized so that suction side pressure equals compression side pressure This is what I read on the suction side (i.e. it will be the same on the compressed side). July 38 psi August 45 psi (so I let out five psi) Sept. 60 psi (so I the let out 20 psi) In other words, even though I let out pressure because it gets so high that the compressor, when started for the first time in the morning, cycles off and on because of the high pressure cut-out circuit. That's why I have to let out pressure so it will get about the business of refrigerating. So where does the excess pressure come from? And, don't say water vapor as there will be no steam even if there is water vapor when the system is cool and stabilized in the morning. -- Sir Gregory |
#6
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
In the morning, before starting, when the system is stabilized so that suction side pressure equals compression side pressure This is what I read on the suction side (i.e. it will be the same on the compressed side). Why do you assume that each side of the system is the same? You've got a pressure gauge on one side. Your problem is consistent with the high readings that you have. Do you really have any idea what the pressure is on the other side? I'd consider that the refrigerant is contaminated. Go through the cleaning process, pressure test and replace the refrigerant. If the problem comes back suspect a leak or a bad compressor. Hope it turns out to be an easy fix. Dave M. |
#7
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
On Sat, 04 Oct 2014 15:28:37 -0400, "Sir Gregory Hall, Esq."
wrote: On Sat, 04 Oct 2014 07:34:51 +0700, wrote: On Fri, 03 Oct 2014 10:38:12 -0400, "Sir Gregory Hall, Esq." wrote: On Fri, 03 Oct 2014 19:08:56 +0700, wrote: On Thu, 02 Oct 2014 15:14:32 -0400, "Sir Gregory Hall, Esq." wrote: I can't figure it out. I keep having to let refrigerant out of my Adler Barbour. It runs great with the suction-side pressure set at 15 psi. But, every month or so it will commence to cycle off and on after being off for the night. I put a gauge on it and the suction side pressure is in the beginning of the red range(55 psi). It turns on and the compressor starts compressing, the pressure starts going down but it only gets to about 45 psi until the compressor *clicks off* and the voltage gauge goes up a volt or two because the load comes off the circuit. Then it turns itself off and back on and the compressor starts to compress again and the pressure goes down to about 45 psi, then it cycles off again. So, I let out some pressure until it only starts out around 45 psi and it will finally keep compressing until it draws down the suction side to about 15 psi where it stabilizes. So where does the extra pressure come from. I've had to let out ten pounds of pressure about half a dozen times this summer. I can understand leaks but this is ridiculous! You have a closed system connected to a compressor. One side to the suction side and the other to the pressure side. Think why the suction side would be at a higher pressure, or conversely, why the low pressure side is at a lower pressure in a properly operating system. Since the two sides are able to equalize when the compressor sits idle overnight the suction side and the compressed side should be the same. So, when I measure the suction side at startup and it shows 50 psi that means the compressed side is also (temporarily) at 50. As the suction side pressure decreases the compressed side increases. So, if I measured pressure on the suction side in Jult after it has sat idle all night it and it starts out being 30psi, do tell why in August it will suddenly be reading 50psi on the same suction side at start up? As I said, it IS a closed system. If the system has been off for a sufficient period the entire system should be the same pressure as the refrigerant will be the same temperature throughout the system. Then you start the system and the compressor sucks on one side and blows on the other as it is a closed system why aren't the two sides of the system still at the same pressure? I fear you may suffer from reading comprehension problems, Bruce. I understand what you just typed and the problem has nothing to do with a system that's running and everything to do with a system that has been turned off for the night. In the morning, before starting, when the system is stabilized so that suction side pressure equals compression side pressure This is what I read on the suction side (i.e. it will be the same on the compressed side). July 38 psi August 45 psi (so I let out five psi) Sept. 60 psi (so I the let out 20 psi) In other words, even though I let out pressure because it gets so high that the compressor, when started for the first time in the morning, cycles off and on because of the high pressure cut-out circuit. That's why I have to let out pressure so it will get about the business of refrigerating. So where does the excess pressure come from? And, don't say water vapor as there will be no steam even if there is water vapor when the system is cool and stabilized in the morning. I've been trying to get you to reason rather then just bitch and moan. Think about why a totally closed system might have a significantly different pressure for the suction and pressure sides of a compressor when running and the same pressure on each side when the system is shut down for a while. You seem to be saying that your stabilized system pressure is high.... Have you checked the temperature of the system -- usually OAT and looked at a temperature - pressure table to be sure that it isn't a temperature problem? -- Cheers, Bruce in Bangkok |
#8
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
On Sun, 05 Oct 2014 10:47:40 +0700, wrote:
On Sat, 04 Oct 2014 15:28:37 -0400, "Sir Gregory Hall, Esq." wrote: On Sat, 04 Oct 2014 07:34:51 +0700, wrote: On Fri, 03 Oct 2014 10:38:12 -0400, "Sir Gregory Hall, Esq." wrote: I've been trying to get you to reason rather then just bitch and moan. Think about why a totally closed system might have a significantly different pressure for the suction and pressure sides of a compressor when running and the same pressure on each side when the system is shut down for a while. You seem to be saying that your stabilized system pressure is high.... Have you checked the temperature of the system -- usually OAT and looked at a temperature - pressure table to be sure that it isn't a temperature problem? He's misreading the gauges, has bad gauges, or is wrong about the system being in a stable state. |
#9
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
On Sun, 05 Oct 2014 07:12:58 -0500, Vic Smith
wrote: On Sun, 05 Oct 2014 10:47:40 +0700, wrote: On Sat, 04 Oct 2014 15:28:37 -0400, "Sir Gregory Hall, Esq." wrote: On Sat, 04 Oct 2014 07:34:51 +0700, wrote: On Fri, 03 Oct 2014 10:38:12 -0400, "Sir Gregory Hall, Esq." wrote: I've been trying to get you to reason rather then just bitch and moan. Think about why a totally closed system might have a significantly different pressure for the suction and pressure sides of a compressor when running and the same pressure on each side when the system is shut down for a while. You seem to be saying that your stabilized system pressure is high.... Have you checked the temperature of the system -- usually OAT and looked at a temperature - pressure table to be sure that it isn't a temperature problem? He's misreading the gauges, has bad gauges, or is wrong about the system being in a stable state. You two are hopeless as you both can't seem to render things down to the basics. The basics are that the suction side and the compressed side will carry the same psi after the system has sat all night long turned off. It doesn't matter where one puts the gauge as the pressure will be the same throughout. The compressor *leaks* and is not some sort of impermeable membrane. Duh. And don't say there is some kind of a check valve in the system as that would also be silly as the evaporator is a free flow device. Silly speculation as to the system being hot might be the problem are just that - silly as the compressor will be at room temperature in the morning. Actually it will be closer to water temperature as it's installed in the bilge. My question of where does the extra psi come from remains unanswered. |
#10
posted to rec.boats.cruising
|
|||
|
|||
My Adler Barbour seems to make refrigerant.
On Sat, 4 Oct 2014 17:38:56 -0400, "David L. Martel"
wrote: In the morning, before starting, when the system is stabilized so that suction side pressure equals compression side pressure This is what I read on the suction side (i.e. it will be the same on the compressed side). Why do you assume that each side of the system is the same? Because the pressure throughout is the same after it has sat all night and has yet to be started in the morning. You've got a pressure gauge on one side. Your problem is consistent with the high readings that you have. Do you really have any idea what the pressure is on the other side? Not physically with a gauge but that would be unnecessary. Every bit as unnecessary as testing the psi in both sides of a balloon. I'd consider that the refrigerant is contaminated. Possibly, I had a leak whereby most of the pressure leaked out. I didn't put the vacuum to it but just added more r134a thinking that since the pressure inside was still higher than atmospheric pressure no contaminating air could have leaked in. Go through the cleaning process, pressure test and replace the refrigerant. If the problem comes back suspect a leak or a bad compressor. Compressor is good as when the pressure is right it cools like a champ. Hope it turns out to be an easy fix. It is easier to just let out excess pressure from time to time although I sure would like a decent explanation as to how in the hell can the pressure increase unless somebody is sneaking aboard and putting more r123a into it from time to time. -- Sir Gregory |
Reply |
|