Home |
Search |
Today's Posts |
#1
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
WE have a new Waeco Coolmatic icebox conversion unit that we installed
earlier this year. This is the unit: http://www.defender.com/product.jsp?path=-1|406|10789|86418&id=323775 This unit uses the Danfoss BD35F compressor & controls. It was installed with an optional Mobitronics AC power supply (when AC is present, solenoid switches from DC to AC). This unit puts out 24V with 110V input - Spec says nominal output voltage is 25V and no-load voltage is 29V. The unit is purpose made for the BD35 compressors. PROBLEM: This weekend, the compressor would not come on for long periods (on AC or DC) - temperature would rise to 48F or so. (Expected about 38F based on setting). Eventually, just when I thought the unit was completely dead), it would kick in and run again. Nothing I did such as switching unit on/off or rotating thermostat to different settings would cause any reaction). Previously, the unit would cycle on and off and maintain temperature in a narrow band. Only change that I can see, is that the batteries were fully charged last night and we were at a different dock (for AC) The Waeco manual says: 12v Cut-in voltage 11.7V Cut-out voltage 10.4V 24V Cut-In voltage 24.2V Cut-Out voltage 22.8V Distance from batteries is about 10 ft. Wire size is 8ga except for Mobitronics unit which has short leads of lighter wiring (about 1ft in/out) Do you think it is possible I am getting cutout due to too HIGH a voltage? (I don't suspect too low, because I have run unit mostly with undercharged batteries with no problem.) I did measure voltage at Refrig teminals (unit not running) but with charger on and it was about 12.7-13V) - I forget 24V number, but I think it was something like 25.2V. GBM |
#2
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
|
#3
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
GBM, Low voltage is the most common cause of start up problems. Low
voltage can be traced to low battery voltage or the boat's electrical circuit. The only way to insure that it is not a voltage problem is to connect a full charged battery directly to the electrical module with proper sized correct polarity jumper cables. The older model BD2.5 and BD3 compressors can indicate a low voltage fault with a LED if one is installed between module terminals C and D. Newer compressors BD35 and BD50 have a full function computer chip like your automobile. You can learn more about LED trouble shooting by viewing the slide show on my web site at http://www.kollmann-marine.com. There are several sections on all these compressors also in my 12/24 Volt Refrigeration Manual. The fan circuit overload will stop the compressor if the fan is faulty. There is a separate set of 12 volt + and - terminals on the module that powers the fan even it compressor is running on 24 volts, for cooling when the thermostat closes. This fan circuit on older units is limited to a maximum of one amp and ½ amp on BD35 and BD50 compressor modules. To eliminate this circuit as a cause for a false compressor start, disconnect the fan wires and any other units connected to these terminals. When eliminating the fan make sure that the thermostat wire is not removed from C terminal on the older models. High amperage overload: The first thing to check is to see that there is adequate air flow through the condenser coil, see if the fan is running or could dust be blocking the coils. To test for overload connect a 10 amp scale ammeter in series with the power wire to the module and watch the start up and running amps. If the start amps exceed 9 amps or the running amps are above 7 amps, when operated on 12 volts, there is an overload. An amperage overload indicates the compressor is faulty or if recently serviced with refrigerant there is a refrigerant problem. The module is more likely to fail than the Compressor but WARNING, do not install a new module on a compressor that test bad with the ohm meter. |
#4
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
For those with an Adler-Barbour, I'd like to inject that the one installed
on the old boat, an Endeavour 35, caused a repetitive buzzing noise.... bzzt....bzzt.....bzzt..............bzzzt..bzzt..bz zt......bzzt....bzzt... on CHANNEL 16 VHF. Only during the bzzt would it open the squelch. It had just enough bzzt that a Standard Eclipse Plus didn't have enough squelch control to shut it out, driving anyone near the speaker SIMPLY MAD by the end of their watch. Took me a while to trace down this bzzt on VHF 16.....until I inadvertently flipped off the wrong breaker, shutting down the damned 12V electronic cold plate....when it just stopped. bzzt....bzzt.....bzzt..............bzzzt..bzzt..bz zt......bzzt....bzzt... bzzt....bzzt.....bzzt..............bzzzt..bzzt..bz zt......bzzt....bzzt... bzzt....bzzt.....bzzt..............bzzzt..bzzt..bz zt......bzzt....bzzt... AAAAAAHAHHHHHHHCCCCCKKKKKk!!!! No other channel, like the ones you never listen to, had any bzzt on them.....ONLY CHANNEL 16. Idiots.... |
#5
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
Thanks Richard - After posting here, I found you site and repeated the
question there, but in more detail. Low voltage is unlikely because batteries were freshly charged - could be a bad connection somewhere - I will check. High/Low voltage is possible if an input range of say 110-120v does not result in 24V within the cutin/out range. Fan circuit overload is possible - I added some insulation above unit - maybe something dropped into fan - I will try vacuuming. I will also try disconnecting the fan. I will also try and get an ammeter installed - I don't like the idea of adding more connections though - Maybe I can get a clamp on type. Funny thing though, once unit does start, it keeps running, so you would not think there could be an overload. I will post this reply to your site too and perhaps we can move discussion there? GBM wrote in message oups.com... GBM, Low voltage is the most common cause of start up problems. Low voltage can be traced to low battery voltage or the boat's electrical circuit. The only way to insure that it is not a voltage problem is to connect a full charged battery directly to the electrical module with proper sized correct polarity jumper cables. The older model BD2.5 and BD3 compressors can indicate a low voltage fault with a LED if one is installed between module terminals C and D. Newer compressors BD35 and BD50 have a full function computer chip like your automobile. You can learn more about LED trouble shooting by viewing the slide show on my web site at http://www.kollmann-marine.com. There are several sections on all these compressors also in my 12/24 Volt Refrigeration Manual. The fan circuit overload will stop the compressor if the fan is faulty. There is a separate set of 12 volt + and - terminals on the module that powers the fan even it compressor is running on 24 volts, for cooling when the thermostat closes. This fan circuit on older units is limited to a maximum of one amp and ½ amp on BD35 and BD50 compressor modules. To eliminate this circuit as a cause for a false compressor start, disconnect the fan wires and any other units connected to these terminals. When eliminating the fan make sure that the thermostat wire is not removed from C terminal on the older models. High amperage overload: The first thing to check is to see that there is adequate air flow through the condenser coil, see if the fan is running or could dust be blocking the coils. To test for overload connect a 10 amp scale ammeter in series with the power wire to the module and watch the start up and running amps. If the start amps exceed 9 amps or the running amps are above 7 amps, when operated on 12 volts, there is an overload. An amperage overload indicates the compressor is faulty or if recently serviced with refrigerant there is a refrigerant problem. The module is more likely to fail than the Compressor but WARNING, do not install a new module on a compressor that test bad with the ohm meter. |
#6
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
On Sat, 22 Jul 2006 15:23:35 -0400, "GBM"
wrote: WE have a new Waeco Coolmatic icebox conversion unit that we installed earlier this year. ...///... Previously, the unit would cycle on and off and maintain temperature in a narrow band. Only change that I can see, is that the batteries were fully charged last night and we were at a different dock (for AC) The Waeco manual says: 12v Cut-in voltage 11.7V Cut-out voltage 10.4V 24V Cut-In voltage 24.2V Cut-Out voltage 22.8V Distance from batteries is about 10 ft. Wire size is 8ga except for Mobitronics unit which has short leads of lighter wiring (about 1ft in/out) Do you think it is possible I am getting cutout due to too HIGH a voltage? /// GBM It certainly looks that way to me. But I am evidently naive in this area: why cut in at 11.7V when the voltage of a freshly charged battery is around 12.5V ?? Brian Whatcott Altus OK |
#7
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
"Brian Whatcott" wrote The Waeco manual says: 12v Cut-in voltage 11.7V Cut-out voltage 10.4V 24V Cut-In voltage 24.2V Cut-Out voltage 22.8V Distance from batteries is about 10 ft. Wire size is 8ga except for Mobitronics unit which has short leads of lighter wiring (about 1ft in/out) Do you think it is possible I am getting cutout due to too HIGH a voltage? /// GBM It certainly looks that way to me. But I am evidently naive in this area: why cut in at 11.7V when the voltage of a freshly charged battery is around 12.5V ?? Brian, These numbers puzzled me too. I think it may mean that the controls will turn the unit off at 10.4v so as to protect the battery and will turn back on again when voltage reaches 11.7v. GBM |
#8
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
On Sat, 22 Jul 2006 22:35:40 -0400, "GBM"
wrote: "Brian Whatcott" wrote The Waeco manual says: 12v Cut-in voltage 11.7V Cut-out voltage 10.4V 24V Cut-In voltage 24.2V Cut-Out voltage 22.8V Distance from batteries is about 10 ft. Wire size is 8ga except for Mobitronics unit which has short leads of lighter wiring (about 1ft in/out) Do you think it is possible I am getting cutout due to too HIGH a voltage? /// GBM It certainly looks that way to me. But I am evidently naive in this area: why cut in at 11.7V when the voltage of a freshly charged battery is around 12.5V ?? Brian, These numbers puzzled me too. I think it may mean that the controls will turn the unit off at 10.4v so as to protect the battery and will turn back on again when voltage reaches 11.7v. GBM Makes sense to me. That means the cause of the misfunction lies elsewhere, I guess Brian Whatcott Altus OK |
#9
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
|
#10
posted to rec.boats.cruising
|
|||
|
|||
Waeco/Adler Barbour refrig - strange behaviour.
GBM wrote:
Thanks Richard - After posting here, I found you site and repeated the question there, but in more detail. Low voltage is unlikely because batteries were freshly charged - could be a bad connection somewhere - I will check. High/Low voltage is possible if an input range of say 110-120v does not result in 24V within the cutin/out range. Fan circuit overload is possible - I added some insulation above unit - maybe something dropped into fan - I will try vacuuming. I will also try disconnecting the fan. I will also try and get an ammeter installed - I don't like the idea of adding more connections though - Maybe I can get a clamp on type. Funny thing though, once unit does start, it keeps running, so you would not think there could be an overload. I will post this reply to your site too and perhaps we can move discussion there? GBM My site and mail is off for a couple of hours on Sundays so I will answer your questions here. 1. If you disconnect shore power from boat the question of high voltage will be eliminated. The BD35 Module can except voltages up to 29 volts before it shuts down compressor. 2. I have no information on Mobiletronics's inverter or how it is wired to the Danfoss module. If one of the safety perimeters of module is being violated there will be a single audible beep coming from module. Is there a beep sound when unit is turned on and unit does no run? Does fan run even if unit does not run? 3. Terminal P on module is only used if low voltage cutout is to be increased so if there is a wire on P terminal remove it and tape the lose end. 4. The only wire to be connected to Module terminal D is a ground wire from troubleshooting LED and that ground is only activated when a module parameter is exceeded. One flash of LED indicates low voltage, Two flashes a fan problem and so on. Low voltage on start may not be detectable with a meter unless you have Superman's eyes. Any resistance connection in wiring anywhere between module and battery will signal module to abort when current starts to flow, that why I recommend by passing all wiring. |