![]() Larry wrote: Once the isolation transformer is between the boat and the power company, the boat only needs TWO WIRES!..the ones to the secondary 120VAC winding! The boat still needs 3 wires just like before. One side of the secondary of the isolation transformer will now go to the BOATS ground system, including the green ground wire on the boat. The secondary of the isolation transformer is treated the same way as your generator system when feeding the boat. Regards Gary |
#2
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]() |
#3
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]()
Larry,
You are correct, but the correct method of connecting an isolation transformer is to use the safety earth at the dock only on the primary side which must be isolated from the hull. Steve "Larry" wrote in message ... "Russell" wrote in news:1150664559.195111.128480 @h76g2000cwa.googlegroups.com: Since my post a few days ago, spoke to our marine electrician and the on-staff electrical expert retained by the Harbor office. We are going to have to install an isolation transformer in our dock box. This will cost about $1,000 after parts, labor and some mods to the box. All 90 boats in our harbor that got the notices have to do this, move, or unplug or disconnect the AC ground from the DC, not a good option. So, now I see the West Advisor says that apparently solves the marina's issue with the AC, but unless we separate all the underwater stuff, like the through hulls, we still are subject to DC corrosion. Can this be true? What is the real solution to the AC, the DC, the safety and the corrosion problem? Is there one? We are one of 90 modest boats from about 28-48 feet, mostly 1970's through 1990's vintage. We all have to get these transformers now, but the issue is what else do we need to do once we are on the transformer? As long as the AC ground on the dock is connected to the DC ground, and therefore all the underwater metal parts of the boat, the electrolysis problems caused by your boat being connected to the earth and all the other boats so connected WILL CONTINUE UNABATED, isolation transformers or no isolation transformers! It's a BATTERY made up of your metal parts, the seawater as electrolyte and the marina metal parts, including the bottom of the harbor the marina is grounded to! You have, by shorting your plate of the battery to the marina plate of the battery, SHORTED OUT THE ELECTROLYSIS BATTERY and its plate is going to be EATEN in the process. AC power is not required to accomplish this, only CHEMISTRY, basic battery chemistry. Now, the secondary winding of the isolation transformer HAS NO GROUND WHATSOEVER, if it is an isolation transformer it isolates its AC power from GROUND. So, you may touch ANY grounded anything, including the AC power ground wire of the power company itself, from EITHER side of the AC output winding of the isolation transformer and you WON'T GET SHOCKED! That's why we call it an ISOLATION transformer....it isolates the AC power going to the boat from GROUND. Once the AC power supply to the boat has no ground connection, whatsoever, you can fully disconnect the boat from shore ground, altogether, and noone will get a shock UNLESS THEY CONNECT THEMSELVES STRAIGHT ACROSS THE TWO OUTPUT WIRES OF THE ISOLATION TRANSFORMER WHERE THE POWER HAPPENS. There are NO other circuits for current to flow through! The only connection from the primary side to the secondary side of an isolation transformer is MAGNETISM IN THE CORE. There are special insulating tapes put between the core of the transformer and the windings to PREVENT any path between them. Geez....this ISN'T ROCKET SCIENCE! Disconnect the damned shore ground from the boat and install the isolation transformer with no secondary ground and it'll be JUST FINE FOR ALL! Once the isolation transformer is between the boat and the power company, the boat only needs TWO WIRES!..the ones to the secondary 120VAC winding! |
#4
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]()
"Steve Lusardi" wrote in
: Larry, You are correct, but the correct method of connecting an isolation transformer is to use the safety earth at the dock only on the primary side which must be isolated from the hull. Steve Correct. The boat must NOT be connected to dock ground to stop the underwater fizzing...(c; |
#5
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]() Russell wrote: Since my post a few days ago, spoke to our marine electrician and the on-staff electrical expert retained by the Harbor office. We are going to have to install an isolation transformer in our dock box. This will cost about $1,000 after parts, labor and some mods to the box. All 90 boats in our harbor that got the notices have to do this, move, or unplug or disconnect the AC ground from the DC, not a good option. So, now I see the West Advisor says that apparently solves the marina's issue with the AC, but unless we separate all the underwater stuff, like the through hulls, we still are subject to DC corrosion. Can this be true? What is the real solution to the AC, the DC, the safety and the corrosion problem? Is there one? We are one of 90 modest boats from about 28-48 feet, mostly 1970's through 1990's vintage. We all have to get these transformers now, but the issue is what else do we need to do once we are on the transformer? You should also be able to install an isolator on your boat, if it does not already have one, and be in compliance of isolating the ground to electrolysis. If an isolator will not function properly in the marina then there is a problem with the marinas wiring, which sounds highly suspect to start with. Ask for the details of how the hired electrician has determined that your boat is causing problems and let us know what he says. What kind of measurements did he do? Regards Gary |
#6
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]() |
#7
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]()
I had a diver under the boat today. This boat was in the yard ten weeks
ago. New shafts, props, all new zincs everywhere (tabs, rudders, shafts, transom, etc.). The diver reports the ZINCS ARE GONE!!! Even most of the bolts are gone or just hanging. How can this be happening? If it is another boat, what can I do to find it or to protect against it without exposing anyone on my boat to AC shock. In the meantime, we are unplugging from shore power, which is scary, although our bilges are pretty dry. I read all the posts, but am still confused on whether it is AC or DC related, and if the isoloation transformer has any impact. Oh, one more thing. We had a new computerized charger installed a while back. I wonder if it were wired incorrectly would that cause the zincs to go like this? Russell wrote: Since my post a few days ago, spoke to our marine electrician and the on-staff electrical expert retained by the Harbor office. We are going to have to install an isolation transformer in our dock box. This will cost about $1,000 after parts, labor and some mods to the box. All 90 boats in our harbor that got the notices have to do this, move, or unplug or disconnect the AC ground from the DC, not a good option. So, now I see the West Advisor says that apparently solves the marina's issue with the AC, but unless we separate all the underwater stuff, like the through hulls, we still are subject to DC corrosion. Can this be true? What is the real solution to the AC, the DC, the safety and the corrosion problem? Is there one? We are one of 90 modest boats from about 28-48 feet, mostly 1970's through 1990's vintage. We all have to get these transformers now, but the issue is what else do we need to do once we are on the transformer? |
#8
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]()
"Russell" wrote in news:1150917215.062248.50070
@p79g2000cwp.googlegroups.com: I had a diver under the boat today. This boat was in the yard ten weeks ago. New shafts, props, all new zincs everywhere (tabs, rudders, shafts, transom, etc.). The diver reports the ZINCS ARE GONE!!! Even most of the bolts are gone or just hanging. How can this be happening? If it is another boat, what can I do to find it or to protect against it without exposing anyone on my boat to AC shock. In the meantime, we are unplugging from shore power, which is scary, although our bilges are pretty dry. I read all the posts, but am still confused on whether it is AC or DC related, and if the isoloation transformer has any impact. Oh, one more thing. We had a new computerized charger installed a while back. I wonder if it were wired incorrectly would that cause the zincs to go like this? It is DC related because your underwater metal parts are hooked directly to the electrical system on the dock's ground wire. This amounts to running a wire from your engine block and underwater metals to every other boat's underwater metals and the entire bottom of the bay. This results in some horrific electrolysis currents, you zincs trying to provide noble metal to protect the whole marina, not just your skeg and prop, eating it away at an amazing pace. When the zinc was gone, the next least noble metal started to be used as the underwater battery plate in the shorted system. Get a digital multimeter from someone. Unplug the boat at the dock post. Put the digital multimeter on DC volts. Put one lead of the meter on the boat's now-open ground pin in the boat power plug. Put the other meter lead on the ground lug (or the metal electrical box bare metal which is the same point). You will now measure the DC potential difference between your boat's underwater metal parts, hooked to the ground pin of the boat's power plug...and the rest of the world hooked to the marina ground, including every other boat that's wired like yours is. This voltage will be around 1-2 volts DC, not AC. Any AC voltage you can measure at this point indicates something is bad wrong with the marina's electrical system. There should be no AC voltage between their ground and your boat's connection to seawater...the underwater metals that are "grounded" to AC ground. If you want to see how much current flows when the boat's plugged in, switch the digital multimeter to DC amps. The internal low-resistance shunt in the multimeter is a virtual short, allowing the boat and AC power system to conduct like it was plugged in. That current you see is why your zincs are eating away just before the nice prop was..... Many problems are caused by the boaters themselves. One boat has a faulty battery charger leaking between the DC output and the charger's ground back to the dock. This results in some DC voltage applied to that boat's underwater metal parts, much more voltage than just zincs can produce and, probably the wrong polarity. His boat is now acting like a PLATING MACHINE!....using your zincs to plate his prop! Some other boat hasn't had a zinc in years so his boat causes a big potential difference to yours and others. To find the offender, you need one person standing watching your DC voltmeter reading high and another person going down the dock, NOT SWITCHING BREAKERS ON AND OFF, but unplugging boats, one after another. FRS walkie talkies make this job much easier than yelling between you. When you unplug the offender, the voltage back on your dock drops drastically. THAT guy is eating everyone's zincs and props. Show the marina dockmaster who has a very good reason to get him OFF YOUR GRID as it's eating the marina's electrical system, too! Let us know which boat has the flea market automatic battery charger when you find him..... Japanese battery chargers some have POSITIVE DC hooked to AC ground!....the only AC ground point on his boat so it doesn't short his batteries to operate that way. His prop is +14.2V above yours!...lotsa ground current flows! |
#9
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]() Russell wrote: Since my post a few days ago, spoke to our marine electrician and the on-staff electrical expert retained by the Harbor office. We are going to have to install an isolation transformer in our dock box. This will cost about $1,000 after parts, labor and some mods to the box. All 90 boats in our harbor that got the notices have to do this, move, or unplug or disconnect the AC ground from the DC, not a good option. So, now I see the West Advisor says that apparently solves the marina's issue with the AC, but unless we separate all the underwater stuff, like the through hulls, we still are subject to DC corrosion. Can this be true? What is the real solution to the AC, the DC, the safety and the corrosion problem? Is there one? We are one of 90 modest boats from about 28-48 feet, mostly 1970's through 1990's vintage. We all have to get these transformers now, but the issue is what else do we need to do once we are on the transformer? Russ, I've never heard such garbage in my life. Lets get this straight, they have a problem with their wiring, and they want you to pay for it? No way. |
#10
![]()
posted to rec.boats.electronics
|
|||
|
|||
![]() While on the subject, would someone please explain the difference between an Isolation Transformer and a Galvanic Isolator? Do they do different things? Is one better to have than the other? Thanks, Gary |